BRICBOX

Drift chamber readout module (see also BRIC)

Maximum supported branch length: 30 readout cards.

BRICBOX send Link Control Frame (LCF) with used defined bits 8:15 as following:

bit

description (send)

0

Suspend (receive buffer is full)

1

Enable remote data loopback **

2

reserved, 0

3

Local Error state

4

Local Ready state

5

Local RX error

7:6

reserved

8

b1_absent

9

b2_absent

10

b1_overflow

11

b2_overflow

12

b1_align_err

13

b2_align_err

14

b1_timeout

15

b2_timeout

31:16

Inverted 15:0

Card autodetect is performed on power-on reset and link reset (5CE) and absent bits are updated.

Status bits (rx error, absent, overflow, align_err, timeout) are cleared on reset (power, 5CE).

Status bits overflow, align_err, timeout are also cleared right after LCF is sent.

Local error = b1_absent & b2_absent

Cable for BRICBOX: ELTRA(37) to IDC-34

НАЗНАЧЕНИЕ

ELTRA(37)

IDC-34

на SCH

Земля

1

NC

Сдвиг возвр

22

23

a12

сдвиг возвр

3

24

b12

Земля

21

NC

Сдвиг

2

21

a11

Сдвиг

20

22

b11

Земля

4,23

NC

Досчет

24

20

b10

Досчет

5

19

a10

Земля

6,25

NC

Парал.загрузка

7

31

a16

Земля

26

32

b16

Мода работы

8

27

a14

Земля

27

28

b14

Вых. 4 разряда

9

33

a32

Земля

27

34

b32

5.2В для терминатора

29

NC

Вх. Для 1 разряда

10

29

a15

Земля

11

30

b15

3 разряд

30

5

a3

Земля

12

6

b3

4 разряд

31

7

a4

Земля

13

8

b4

2 разряд

32

3

a2

Земля

14

4

b2

1 разряд

33

1

a1

Земля

15

2

b1

7 разряд

34

13

a7

Земля

16

14

b7

8 разряд

35

15

a8

Земля

17

16

b8

5 разряд

36

9

a5

Земля

18

10

b5

6 разряд

37

11

a6

Земля

19

12

b6


BRICBOX

BRICBOX (last edited 2011-12-22 14:15:46 by slepnev)